Design (continued)

Isolation (Functional)

Alarm Outputs

Controller Output Types

Controller Output Algorithms

AC Power: Is electrically isolated from all other inputs and outputs to withstand a HIPOT potential of 1900 Vdc for 2 seconds per Annex K of EN61010-1.

Analog Inputs and Outputs: Are isolated from each other and all other circuits at 850 Vdc for 2 seconds.

Digital Input and Digital Output: Are isolated from all other circuits at 850 Vdc for 2 seconds.

Relay Contacts: With a working of 115/230 Vac, isolated from each other and all other circuits at 345 Vdc for 2 seconds.

One SPDT electromechanical relay.

A second alarm is available using the second control relay. This is not available with Relay Duplex, Position Proportional, or Three Position Step control.

Alarm Relay Contacts Rating

Resistive Load: 5 ampere at 120 Vac or 30 Vdc, 2.5 A at 240 Vac.

Current Output (Isolated)

Range can be set anywhere between 0 to 21 mA, and as direct or reverse action. Resolution: 11 bits for 0 to 21 mA

Accuracy: 0.5 % full scale

Temperature Stability: 0.1 % F.S./°C

Load Resistance: 0 to 1000 ohms

Electromechanical Relays (One or Two)

SPDT contacts. Both Normally Open and Normally Closed contacts are brought out to the rear terminals.

Internally socketed

Resistive Load: 5 amps @ 120 Vac or 30 Vdc, 2.5A at 240 Vac

Inductive Load: 50 VA @ 120 Vac or 240 Vac

Motor: 1/6 H.P.

Solid State Relays (One or Two)

SPST solid state contacts consisting of a triac N.O. output.

Internally socketed

Resistive Load: 1.0 amp @ 25 °C and 120 or 240 Vac

0.5amp @ 55 °C and 120 or 240 Vac

Inductive Load: 50 VA @ 120 Vac or 240 Vac

Minimum Load: 20 milliamps

Open Collector Outputs (One or Two)

Maximum Sink Current: 20 mA

Overload Protection: 100 mA

Internally powered @ 30 Vdc

Opto-isolated from all other circuits except current output, but not from each other. Socketed jumper assembly replaces relay.

Solid State Relays (10 amps)

One or two externally mounted SPST triac N.O. outputs for use with open collector outputs.

Resistive Load:

15 amps @ 25 °C and 120 or 240 Vac

 

10 amps @ 55 °C and 120 or 240 Vac

Inductive Load:

50 VA @ 120 Vac or 240 Vac

Motor Rating:

1 HP @ 25 °C

 

0.75 HP @ 55 °C

 

 

See Section 4.7.

 

 

 