Alarm on totalizer value

Totalizer reset via digital input

The alarm type configuration includes an Alarm on Totalizer value. This allows an alarm setpoint value to be used to cause an alarm when exceeded. The alarm setpoint represents the lowest four digits of the selected Totalizer Scale Factor and has a range from 0 to 9999 x Totalizer Scale Factor.

The digital input type configuration includes a Reset Totalizer that resets the accumulated totalizer value when the DI is closed.

4/00

UDC 3300 Controller Product Manual

185

Page 197
Image 197
Honeywell UDC 3300 manual Alarm on totalizer value Totalizer reset via digital input