3.6Loop 1 Tuning Parameters Set Up Group

Function prompts

Table 3-3 lists all the function prompts in the Tuning Set Up group. How the Algorithm and Control Set Up groups are configured determines which prompts will appear.

Function Prompt

Lower Display

PROP BD

or

GAIN

or

GAINVALn***

Table 3-3 Tuning Group Function Prompts

Function

Selections or

Name

Range of Setting

 

Upper Display

 

 

Proportional Band

0.1 to 9999 %

or

 

Gain

0.001 to 1000

or

 

Gain Value being used by

Read Only

Gain Scheduling when

 

enabled in Control Setup

 

group “PID SETS”

 

Factory Setting

- -

1.000

- -

Refer

to

Section

4.2

RATE MIN

RSET MIN

or

RSET RPM

MAN RSET

PROPBD2

or

GAIN 2

RATE2MIN

RSET2MIN

or

RSET2RPM

CYC SEC*

or

CYC SX3*

CYC2 SEC*

or

CYC2 SX3*

SECURITY

LOCKOUT

Rate in Minutes

Reset in minutes/repeat or

Reset in repeats/minute

Manual Reset

Proportional Band 2 or

Gain 2

Rate 2 in Minutes

Reset 2 in minutes/repeat or

Reset 2 in repeats/minute

Cycle Time (Heat)

Cycle Time (Cool)

Security Code

Configuration Lockout

0.00to 10.00 minutes

0.02to 50.00

–100 to 100 % output

0.1 to 9999 %

0.001 to 1000

0.00to 10.00 minutes

0.02to 50.00

1 to 120

1 to 120

0 to 4095

NONE

CALIB

+CONF

+VIEW MAX

0.00

1.00

- -

0

- -

1.000

0.00

1.00

- -

20

20

0

CALIB

AUTO MAN**

Manual/Auto Key Lockout

DISABL

 

 

ENABLE

SP SEL**

Setpoint Select Key Lockout

DISABL

 

 

ENABLE

ENABLE

ENABLE

*Cycle times are in either 1 second or 1/3 second increments, depending upon the RLY TYPE configuration in the Output Algorithm Set Up group.

**Only appears if LOCKOUT = NONE.

***Requires Math software option

42

UDC 3300 Process Controller Product Manual

4/00

Page 54
Image 54
Honeywell UDC 3300 manual Loop 1 Tuning Parameters Set Up Group, Function prompts, Function Prompt, Factory Setting, Refer