Procedure #6

Table 9-13 explains how to troubleshoot Alarm Relay Output failure.

Table 9-13 Troubleshooting Alarm Relay Output Failure

Step

1

2

3

4

What to do

Check the alarm configuration data. If it is correct, check the field wiring.

Check that the applicable alarm relay actuates properly depending on what you have set at prompt AxSxTYPE.

If it does, check the field wiring.

Check the field wiring.

Change MCU/Output board.

How to do it

Reconfigure if necessary.

Refer to Section 3 - Configuration for details.

If the alarm type is set for PV, place the controller in manual mode. Vary the input to raise and lower the PV around the setpoint. Listen for a click from the relay as the PV moves in either direction and note that the proper ALM1 or ALM2 is lit.

EXAMPLE: If the alarm is set for MANUAL, put the controller into manual mode. The alarm light is ON. Put the controller into automatic mode and the alarm light is OFF.

Make sure the NO or NC contact wiring is correct on the alarm output terminals.

Refer to Section 2 - Installation for details.

Refer to Table 9-23.

258

UDC 3300 Controller Product Manual

4/00

Page 270
Image 270
Honeywell UDC 3300 manual explains how to troubleshoot Alarm Relay Output failure, Procedure #6