Step

6

7

8

Operation

Change setpoint during Hold mode

End the Ramp

Disable the setpoint ramp function

Press

or

SET UP

FUNCTION

LOOP 1/2

Action

to change the “HELD” setpoint if the ramp is on “HOLD.”

However, the ramp time remaining is not changed. Therefore, when returning to RUN mode, the setpoint will ramp at the same rate as prior to local setpoint changes and will stop if the final setpoint is reached before time expires.

If the time expires before the final setpoint is reached, it will jump to the final setpoint.

When the final setpoint is reached, the

“R” changes to “H” in the upper display and the controller operates at the new setpoint.

ATTENTION Any time the local setpoint is different from the final setpoint value and

the RUN/HOLD key is pressed, the ramp will start again.

until you see:

Upper Display

SET UP

Lower Display

SP RAMP

You will see:

Upper Display

DISABL— Disables SP Ramp

Lower Display ENABLE— Enables SP Ramp for Loop 1 ENABL2— Enables SP Ramp for Loop 2

SP RAMP ENAB12— Enables Sp Ramp for Loops 1 and 2

9

Return to normal operating mode

until you see:

Upper Display

DISABL

Lower Display

SP RAMP

LOWER

DISPLAY

4/00

UDC 3300 Controller Product Manual

167

Page 179
Image 179
Honeywell manual UDC 3300 Controller Product Manual 167