Function

External Program

Reset

“To Begin”

Keyboard Reset

Viewing the present

ramp or soak

segment number

and time

Press

RUN

HOLD

LOWER DISPLAY

LOWER DISPLAY

Result

If Remote Switching (Digital Input option) is present on your controller, contact closure resets the SP Program back to the start of the first segment.

Program cycle number is not affected.

Reopening the contact has no effect and places the program in HOLD mode.

The setpoint is changed to what the setpoint was when the program was first started.

restarts the Setpoint Program

until you see

Upper Display

Lower Display

ToBEGIN

Press [] key to reset program to beginning at Hold state.

until you see

Upper Display

R” and the PV value

Lower Display

For Ramp segments:

# RA XX.XX

Ramp Time - Hours.Minutes or

Ramp Rate - EU/MIN or EU/HR

Indicates Ramp segment

Segment Number (odd only)

For Soak segments:

# SK XX.XX

Time remaining in segment in Hrs.Minutes including current partially completed minute

Indicates Soak segment

Segment Number (even only)

4/00

UDC 3300 Controller Product Manual

215

Page 227
Image 227
Honeywell UDC 3300 manual # Ra