Figure 4-1 Example of Mass Flow Compensation using Multiplier/Divider Algorithm, continued

Example - Mass Flow Compensation

Determined value of K:

 

 

 

 

 

 

K 2 =

1

x

 

Tref

=

600

= 0.14914

 

 

 

 

(90) (44.7)

90

 

 

Pref

 

 

Therefore K = 0.386

 

 

 

 

Q SCFM = (0.386) (650)

 

DPf (in H2O) (IN3 + 14.7)

 

 

 

 

 

 

 

 

(IN2 + 460)

 

K

(Calc HI - Calc LO )

Summary of Flow Values At Values Conditions

Reference Conditions

Temp (Tf )

Pressure (Tf )

Flow (SFCM)

 

DPf = 45" H 2O (50%)

DPf

= 90" H2 O (100%)

 

( R)

(psia)

 

 

 

 

 

 

140

F + 460

30 psi + 14.7

459

 

650

 

 

 

 

 

 

170

F + 460

50 psi + 14.7

539

 

763

 

 

 

 

 

 

170

F + 460

20 psi + 14.7

395

 

559

 

 

 

 

 

 

110

F + 460

50 psi + 14.7

567

 

802

 

 

 

 

 

 

110

F + 460

20 psi + 14.7

415

 

587

 

 

 

 

 

 