Lower Display

Prompt

OUT2 ALG

RLYSTATE

RLY TYPE

Upper Display

Range of Setting

or Selection

NONE

TIME

CURRNT

CUR D

CUR TI

TI CUR

1OF2OF

1ON2OF

1OF2ON

1ON2ON

MECHAN

SOL ST

Parameter

Definition

The OUTPUT ALGORITHM lets you select the type of output you want for the second control loop

See OUT ALG for definitions.

NONE

TIME SIMPLEX

CURRENT SIMPLEX (AUX OUT)

CURRENT DUPLEX (AUX OUT)

CURRENT/TIME DUPLEX

TIME/CURRENT DUPLEX

ATTENTION If Time Duplex or TPSC is selected as the first control loop output, then TIME, CUR TI, and TI CUR are not available as the second control loop output.

DIGITAL OUTPUT STATUS AT 0 % OUTPUT allows the following selections:

1OF2OF

Output 1 de-energized

 

Output 2 de-energized

1ON2OF

Output 1 energized

 

Output 2 de-energized

1OF2ON

Output 1 de-energized

 

Output 2 energized

1ON2ON

Output 1 energized

 

Output 2 energized

 

 

RELAY CYCLE TIME INCREMENT selection is used only for Time Simplex and Duplex output configurations and affects both loops. This configuration sets the increment size of the relay cycle times in the Tuning and Tuning 2 Set Up groups.

ELECTROMECHANICAL RELAY— Cycle time in one- second increments.

SOLID STATE RELAY— Cycle time in 1/3 second increments. This is useful for solid state relay applications that require shorter cycle times. DO NOT use this setting unless cycle times of less than 1 second are required.

The Lockout selection must be set to NONE in order to view this selection.

4/00

UDC 3300 Process Controller Product Manual

111

Page 123
Image 123
Honeywell UDC 3300 manual OUT2 ALG Rlystate RLY Type, 1OF2OF