Permissible wire bundling

Table 2-3 shows which wire functions should be bundled together.

NOTE

For installation where high EMI/RFI noise cannot be avoided, we

 

recommend you use shielded twisted pair wires for the signals in bundle 2.

Table 2-3 Permissible Wiring Bundling

Bundle No.

1

2

3

Wire Functions

Line power wiring

Earth ground wiring

Control relay output wiring

Line voltage alarm wiring Analog signal wire, such as:

Input signal wire (thermocouple, 4 to 20 mA, etc.)

4-20 mA output signal wiring

Slidewire feedback circuit wiring

Digital input signals

Communications

Low voltage alarm relay output wiring

Low voltage wiring to solid state type control circuits

Identify your wiring requirements

To determine the appropriate diagrams for wiring your controller, refer to the model number interpretation in this section. The model number of the controller can be found on the inside of the case.

16

UDC 3300 Controller Product Manual

4/00

Page 28
Image 28
Honeywell UDC 3300 manual Shows which wire functions should be bundled together, Permissible wire bundling