8.4 Auxiliary Output Calibration

Introduction

Calibrate the controller so that the Auxiliary output provides the proper

 

amount of current over the desired range. The controller can provide an

 

auxiliary output current range of from 0 to 21 milliamperes and can be

 

calibrated at 4 mA for 0 % of output and 20 mA for 100 % of output or

 

any other values between 0 mA and 21 mA.

Equipment needed

Calibrator connections

You will need a standard shop type milliammeter with whatever accuracy is required, capable of measuring 0 to 20 milliamps.

Referring to Figure 8-2, wire the controller according to the procedure given in Table 8-4.

Table 8-4 Set Up Wiring Procedure for Auxiliary Output

Step

1

2

3

Action

Apply power and allow the controller to warm up 30 minutes before you calibrate.

Tag and disconnect the field wiring, at the rear of the controller, from terminals 16 (+) and 17 (–). See Figure 8-2.

Connect a milliammeter across these terminals.