4.12 Loop 2 Control Parameters Set Up Group

Introduction

Control 2 group prompts

The functions listed in this group deal with how Loop 2 of a Two-Loop process controller will control the process including: PV source, Number of tuning parameter sets, Setpoint source, Tracking, Power-up recall, Setpoint limits, Output direction, rate and limits, Dropoff, Deadband, and Hysteresis.

Only available on Expanded Model DC330E-XX-XXX.

Table 4-11 lists all the function prompts in the Control 2 Set Up group and their definitions.

Table 4-11 Control 2 Group Definitions

Lower Display

Prompt

PV 2 SRC

Upper Display

Range of Setting

or Selection

INP 1

INP 2

IN AL1

IN AL2

INP 3

Parameter

Definition

PROCESS VARIABLE 2 SOURCE— Select the source of the Process Variable for Loop 2.

INPUT 1

INPUT 2

INPUT ALGORITHM 1

INPUT ALGORITHM 2

INPUT 3

FORCE MA

PID SETS

 

FORCE MANUAL/AUTO links Auto/Manual modes. If

 

either loop changes mode due to a front panel change,

 

digital input action, or failsafe action, the other loop tracks

 

that mode.

 

 

DISABL

DISABL— Disables FORCE MA.

 

LINK12

LINK12— Links modes for both loops.

 

 

 

 

 

 

NUMBER OF TUNING PARAMETER SETS— This

 

selection lets you choose one or two sets of tuning

 

constants (gain, rate, and reset).

 

1 ONLY

ONE SET ONLY— Only one set of tuning parameters is

 

available. Configure the values for:

 

 

 

Gain (proportional band)

 

 

 

Rate

 

 

 

 

Reset Time

 

 

 

 

Cycle Time (if time proportional is used)

2KEYBD

TWO SETS KEYBOARD SELECTABLE— Two sets of

 

tuning parameters can be configured and can be selected

 

at the operator interface or by using the Digital Inputs.

 

 

 

 

 

Press

LOWER DISPLAY

key until you see PID SET3 or

 

PID SET4 then press

or

to switch between

 

sets. Configure the values for:

 

 

 

Gain #3, Rate #3 , Reset #3, Cycle #3 Time

 

 

Gain #4, Rate #4, Reset #4, Cycle #4 Time

 

See Subsection 5.10 for procedure.

 

 

 

 

 

 

124

UDC 3300 Process Controller Product Manual