4.13 Options Set Up Group

Introduction

Configure the remote mode switch (Digital Inputs) to a specific contact

 

closure response, or configure the Auxiliary Output to be a specific

 

selection with desired scaling.

Option group prompts

Lower Display

Prompt

Table 4-12 lists all the function prompts in the Options Set Up group and their functions.

Table 4-12

Options Group Definitions

 

 

 

Upper Display

 

Parameter

Range of Setting

 

Definition

or Selection

 

 

 

 

 

AUX OUT

or

CUR OUT2*

ATTENTION Prompts for the Auxiliary Output Selection appear only if one of the Auxiliary Output boards is installed.

*DE330E only

DISABL

INP 1

AUXILIARY OUTPUT SELECTION FOR ONE LOOP

or

AUXILIARY OUTPUT SELECTION FOR TWO LOOPS

This selection provides an mA output representing one of several control parameters. The display for auxiliary output viewing will be in engineering units for all but output. Output will be displayed in percent.

Other prompts affected by these selections: 4mA VAL and 20mA VAL.

ATTENTION When the controller is configured for Two- Loop operation, and the Loop 2 Output selection requires a current output, the Auxiliary Output selection is automatically set to Output 2 and all other selections are locked out.

ATTENTION Output cannot be configured when Three Position Step Control is used.

NO AUXILIARY OUTPUT

INPUT 1— This represents the configured range of input 1.

FOR EXAMPLE:

Type J Thermocouple (0 °F to 1600 °F) 0 °F display = 0 % output

1600 °F display = 100 % output

INP 2

INP 3

CB OUT

INPUT 2 represents the value of the configured range of input 2.

INPUT 3 represents the value of the configured range of input 3.

CONTROL BLOCK OUTPUT— Represents the uncharacterized use of automatic control valve which allows the characterizer to characterize the output on Analog Output 1 and the Auxiliary Output to use the uncharacterized output value as Output 2.

PV

PROCESS VARIABLE— Represents the value of the Process Variable. PV = Input XxRatioX + BiasX

4/00

UDC 3300 Process Controller Product Manual

129

Page 141