Function Prompt

Lower Display

RECYCLES

SOAK DEV

PROG END

STATE

KEYRESET

HOTSTART

SEG1RAMP or

SEG1RATE

SEG2 SP

SEG2TIME

SEG3RAMP or

SEG3RATE

SEG4 SP

SEG4TIME

SEG5RAMP or

SEG5RATE

SEG6 SP

SEG6TIME

SEG7RAMP or

SEG7RATE

SEG8 SP

SEG8TIME

SEG9RAMP or

SEG9RATE

SG10 SP

SG10TIME

SG11RAMP or

SG11RATE

SG12 SP

SG12TIME

Function

Name

Number of Program

Recycles

Guaranteed Soak Deviation Value

Program Termination State

Program State at Program End

Reset/Rerun SP Program

Hot Start

Segment #1 Ramp Time or Segment #1 Ramp Rate

Segment #2 Soak Setpoint Value

Segment #2 Soak Duration

Same as above

Selections or

Range of Setting

Upper Display

0 to 99 recycles

0 to 99

The number selected will be the PV value (in engineering units) above or below the setpoint outside of which the timer halts.

LASTSP (Hold at last setpoint in the program)

F SAFE (Manual mode/Failsafe output)

DISABL

HOLD

DISABL

TOBEGN

RERUN

DISABL

ENABL

0-99 hours.0-59 minutes Engineering units/minute or Engineering units/hour

Select TIME, EU/MIN, or EU/HR at prompt RAMPUNIT. All ramps will use the same selection.

Within the Setpoint limits

0-99 hours.0-59 minutes

Selections are same as above.

Factory Setting

––

––

––

––

DISABL

DISABL

––

––

––

––

Refer

to

Section

4.4

*Requires SP Programming option

46

UDC 3300 Process Controller Product Manual

4/00

Page 58