Step

 

 

 

 

 

 

Press

SET

 

Press

FUNC

to

UP

 

 

 

to Select Set

Select

 

Up Group

Function

 

 

 

 

Prompts

 

 

 

 

 

 

 

Press ▲ ▼

 

to Enter

Remarks

Value or

 

Selection

 

 

 

4

5

6

Algorithm

CONT ALG

Tuning

RSET2MIN

 

GAIN2

 

 

 

RATE2MIN

 

 

Options

DIG IN1 or

 

DIG IN2

PID A

50.00

See Note 1

0.00

AM STA

Defines back-up control algorithm.

Note 1. Set the Gain 2 equal to

Input 1 Span

Input 2 Span

If “PB” is selected under the Control Set Up group function prompt “PBorGAIN”, set the PROP BD2 to

Input 2 Span

100 x Input 1 Span

Select PIDSET 1 tuning parameters as needed by the application.

CAUTION

Operation

DO NOT SELECT

In the CONTROL set up list, do not select SP TRACK as PV or RSP.

In the SP RAMP set up list, do not select SP RATE as ENABLE.

In the ALGORTHM set up list, do not select CONT ALG as PID B, ON-OFF, or 3PSTEP.

In the Display menu when PIDSET # is displayed, DO NOT change the selection.

Set the local setpoint 2 to 0 % of the Input 2 range.

These features work with the Auto/Manual Station.

In the SP RAMP set up list, SP PROG (acts on SP1 for backup operation).

In the SP RAMP set up list, SP RAMP (acts on SP1 for backup operation).

In the CONTROL set up list, ACTION as DIRECT or REVERSE for the backup PID A operation.

The PD+MR action is forced to be DIRECT as required for the pass through of the output signal.

192

UDC 3300 Controller Product Manual

4/00

Page 204
Image 204