4.16 Display Parameters Set Up Group

Introduction

Display group prompts

Lower Display

Prompt

DECIMAL

DECIMAL2

TEMP UNIT

PWR FREQ

RATIO 2

This group includes selections for Decimal place, Units of temperature, and Power frequency.

Table 4-15 lists all the function prompts in the Display Set Up group and their definitions.

Table 4-15

Display Group Definitions

 

 

 

 

 

Upper Display

 

 

 

Parameter

Range of Setting

 

 

 

Definition

or Selection

 

 

 

 

 

 

 

 

 

 

 

 

DECIMAL POINT LOCATION FOR LOOP 1— This

 

 

 

selection determines where the decimal point appears in

 

 

 

the display.

XXXX

 

 

XXXX— No Decimal Place— fixed, no auto-ranging

XXX.X

 

 

XXX.X— One Place

XX.XX

 

 

XX.XX— Two Places

X.XXX

 

 

X.XXX— Three Places

 

 

 

 

 

 

 

 

ATTENTION

Auto-ranging will occur for selections of

 

 

 

one, two, or three places.

 

 

 

DECIMAL POINT LOCATION FOR LOOP 2— This

 

 

 

selection determines where the decimal point appears in

 

 

 

the display for Loop 2.

XXXX

 

 

XXXX— No Decimal Place— fixed, no auto-ranging

XXX.X

 

 

XXX.X— One Place

XX.XX

 

 

XX.XX— Two Places

X.XXX

 

 

X.XXX— Three Places

 

 

 

 

 

 

 

ATTENTION

Auto-ranging will occur for selections of

 

 

 

one, two, or three places.

 

 

 

TEMPERATURE UNITS FOR BOTH LOOPS— This

 

 

 

selection will affect the indication and operation.

DEG F

 

 

DEG F— Degrees Fahrenheit

DEG C

 

 

DEG C— Degrees Centigrade

NONE

 

 

NONE— No display of units

60 HZ

 

 

POWER LINE FREQUENCY— Select whether your

50 HZ

 

 

controller is operating at 50 or 60 Hertz.

 

 

 

 

 

 

 

ATTENTION

For controllers powered by +24 Vdc, this

 

 

 

configuration should be set to the AC line frequency used

 

 

 

to produce the +24 Vdc supply.

 

 

 

Incorrect setting of this parameter can cause normal mode

 

 

 

noise problems in the input readings.

 

 

 

INPUT 2 RATIO— This enables the Ratio for Input 2 to be

 

 

 

set from the front panel. Input 2 must be installed and

 

 

 

enabled for this configuration to operate.

DISABL

 

 

DISABLE— Disables setting Ratio 2 from front panel.

ENABLE

 

 

ENABLE— Allows the Ratio for Input 2 to be set through

 

 

 

the keyboard.

4/00

UDC 3300 Process Controller Product Manual