Table 4-5 Algorithm Group Definitions, Continued

Lower Display

Prompt

Upper Display

Range of Setting

or Selection

Parameter Definition

TOTALIZE

ΣXXXXXXX

TOT SCAL

TOT SEC

ΣRSET ?

DISABL

INPUT1

IN AL1

IN AL2

Σ*En

*E0 = 1 x 100 = 1

*E1 = 1 x 101 = 10

*E2 = 1 x 102 = 100

*E3 = 1 x 103 = 1,000

*E4 = 1 x 104 = 10,000

*E5 = 1 x 105 = 100,000

*E6 = 1 x 106 = 1,000,000

UNLOCK

LOCK

NO

YES

TOTALIZER FUNCTION calculates and displays the total flow volume as measured by Input 1 or applied to either Input Algorithm 1 or Algorithm 2 to totalize the compensated flow rate being calculated by the algorithm. Displayed value is eight digits with a configurable scale factor.

DISABLE— Disables the totalizer function. INPUT 1— Totalizer is applied to Input 1.

IN AL1— Totalizer is applied to Input Algorithm 1. IN AL2— Totalizer is applied to Input Algorithm 2.

ATTENTION The totalizer should always be reset to initialize the counters whenever it is enabled. Otherwise, the Σ (sigma) display will blink.

READ ONLY

Current Scale Factor (Upper Display)

Actual Current Totalized Value (Lower Display)

TOTALIZER SCALE FACTOR— Selects the desired Scale Factor (i.e., Multiplier).

The desired factor is applied to the calculated value to extend the maximum flow range that can be displayed.

TOTALIZER RESET LOCK— Allows the totalizer to be reset.

UNLOCK— Allows the totalizer value to be reset. LOCK— Prevents the totalizer value from being reset.

TOTALIZER RESET— Appears only if the totalizer is unlocked.

NO— No Reset

YES— Resets on next FUNCTION key press and

displays the reset value.

4/00

UDC 3300 Process Controller Product Manual