7.2 Minimum and Maximum Range Values

Select the range values You should calibrate the controller for the minimum (0 %) and maximum (100 %) range values of your particular sensor. If you have a two-input controller, calibrate each input separately.

Select the Voltage or Resistance equivalent for 0 % and 100 % range values from Table 7-1. Use these value when calibrating your controller.

Table 7-1 Voltage and Resistance Equivalents for 0 % and 100 % Range Values

Sensor Type

Thermocouples

PV Input Range

° F

° C

Range Values

0 %

100 %

B

E

E(low)

J

J(low)

K

K(low)

NiNiMoly (NNM68)

NiNiMoly (low)

NiMo-NiCo (NM90)

NiMo-NiCo (low) Nicrosil Nisil (Nic)

R S T

T (low) W5W26 W5W26 (low)

Honeywell Radiamatic

Type RH

Type RI*

RTD

(IEC Alpha=0.00385)

100ohms

100 ohms (low)

200ohms

500ohms

Linear

0 to 3300

-454 to 1832

-200 to 1100

0 to 1600

20 to 770

0 to 2400

–20 to 1000

32 to 2500

32 to 1260

32 to 2500

32 to 1260

0 to 2372

0 to 3100

0 to 3100

-300 to 700

-200 to 500

0 to 4200

0 to 2240

0 to 3400

0 to 9999 max.

-300 to 1200 -300 to 300 -300 to 1200 -300 to 1200

–18 to 1816

–270 to 1000

–129 to 593

–18 to 871

–7 to 410

–18 to 1816

–29 to 538

0to 1371

0to 682

0to 1371

0to 682

–18 to 1300

–18 to 1704

–18 to 1704

–184 to 371

–129 to 260

–18 to 2315

–18 to 1227

–18 to 1871 –18 to 9999 max.

–184 to 649 –184 to 149 –184 to 649 –184 to 649

–0.100 mV

–9.835 mV

–6.472 mV

–0.886 mV

–0.334 mV

–0.692 mV

–1.114 mV

0.000 mV

0.000 mV

0.000 mV

0.000 mV

–0.461 mV

–0.090 mV

–0.092 mV

–5.341 mV

–4.149 mV

–0.234 mV

–0.234 mV

0.00mV

0.00mV

25.18ohms

25.18ohms

50.36ohms

125.90 ohms

13.769 mV

76.373 mV

44.455 mV

50.060 mV

22.400 mV

52.952 mV

22.255 mV

71.330 mV

31.820 mV

71.773 mV

31.825 mV

47.513 mV

20.281 mV

17.998 mV

19.097 mV

12.574 mV

37.075 mV

22.283 mV

57.12mV

60.08mV

329.13ohms

156.90ohms

658.26ohms

1645.65 ohms

Milliamps

Millivolts

Volts

Carbon

Oxygen

4 to 20 mA

0 to 20 mA

0 to 10 mV

0 to 50 mV

1 to 5 Volts

0 to 5 Volts

0 to 10 Volts

0 to 1250 mV

–30 to 510 mV

4.00mA

0.00mA

0.00mV

0.00mV

1.00Volts

0.00Volts

0.00Volts

0.00mV

–30.00 mV

20.00mA

20.00mA

10.00mV

50.00mV

5.00Volts

5.00Volts

10.00Volts

1250 mV

510.00 mV

*User must enter the range manually per RI type and application.

ATTENTION

Thermocouple voltages are for a reference junction temperature of 32 °F (0 °C).