3.9Accutune Set Up Group

Introduction

The Accutune Set Up group offers these selections:

 

FUZZY

 

 

Fuzzy Overshoot Suppression—Uses fuzzy logic to suppress or

 

 

eliminate any overshoot that may occur when the PV approaches

 

 

setpoint.

 

TUNE

 

 

Demand Tuning—The tuning process is initiated through the operator

 

 

interface keys or via a digital input (if configured). The algorithm then

 

 

calculates new tuning parameters and enters them in the tuning group.

 

 

TUNE does operate with 3 Position Step Control.

 

SP*

 

 

SP Tuning—SP tuning continuously adjusts the PID parameters in

 

 

response to setpoint changes. You can select tuning on minimum

 

 

setpoint changes of 5 % up to 15 % span. Perform SP tuning after you

 

 

have configured the controller.

 

 

SP tuning does not operate with 3 Position Step Control algorithm.

 

TUN+PV*

 

 

or

 

 

SP+PV*

 

 

PV Tuning—The (TUNE) Demand Tuning or the (SP) Setpoint

 

 

Tuning portions of these selections work as stated above. PV Adapt

 

 

will occur during Process Variable (PV) disturbances (0.3 % span or

 

 

larger) which result from non-linearities, process dynamics, load

 

 

changes, or other operating conditions. When this condition exists, the

 

 

controller monitors the process response for 1 and 1/2 process cycles

 

 

around the setpoint to determine whether there has been a true process

 

 

change or a momentary upset.

 

 

Process retuning occurs as the process dynamics are learned. When the

 

 

process is being learned with possible retune, a t is shown in the upper

 

 

left display digit.

*SP + PV Tuning not available on Basic Model DC330B.

4/00

UDC 3300 Process Controller Product Manual

47