4.9Input 2 Parameters Set Up Group

Introduction

Input 2 group prompts

Lower Display

Prompt

These are the parameters required for Input 2: actuation, transmitter characterization, high and low range values in engineering units, ratio, bias, filter, burnout, and emissivity.

ATTENTION Prompts for Input 2 appear only if the Input 2 PWA is installed. If the Loop1 Control Algorithm is set for PID A, PID B, or PD+MR and the Loop1 Output Algorithm is set for Position Proportional then the Input 2 configuration prompts are not displayed.

Table 4-8 lists all the function prompts in the Input 2 Set Up group and their definitions.

Table 4-8

Input 2 Group Definitions

 

 

 

Upper Display

 

Parameter

Range of Setting

 

Definition

or Selection

 

 

 

 

 

IN2 TYPE

ATTENTION

Changing the input type will result in the loss of Field Calibration values and will restore Factory Calibration values.

Same as for Input 1 (except Carbon and Oxygen are not used) plus:

SLIDEW*

INPUT 2 ACTUATION TYPE – This selection determines what actuation you are going to use for Input 2.

SLIDEWIRE

*If the Loop 1 Output Algorithm is set for Position Proportional, then the Input 2 actuation is forced to slidewire (SLIDEW). If Loop 1 Control Algorithm is set for Three Position Step Control, then the SLIDEW setting allows the motor position to be shown on the Lower Display. The SLIDEW setting is not available on two-loop or cascade controllers.

XMITTER2 ANALYTIC IN2 HI IN2 LO RATIO 2 BIAS IN2 FILTER 2 BURNOUT2 EMISSIV2

Input 2 ranges and selections are same as for Input 1.

Refer to Input 1 parameters for definitions.

116

UDC 3300 Process Controller Product Manual

4/00

Page 128
Image 128