Position proportional output connections

Figure 2-14 shows the Output and Alarm wiring connections for models with Position Proportional Output or Three Position Step Control (Models

DC330X-EE-XXX-X2, DC330X-AA-XXX-X2).

Calibration

Figure 2-14

For Control and Alarm Relay Contact information, see Tables 2-7 and 2-8.

Position Proportional Output or Three Position Step models must have the output calibrated after installation (see Section 8—Position Proportional Output Calibration) to ensure that the displayed output (slidewire position) agrees with the actual final control element position.

Three Position Step models only require that the motor time be entered. Full calibration is not required.

Position Proportional Output or Three Position Step—Models DC330X-EE-XXX-X2, DC330X-AA-XXX-X2

 

 

 

 

Motor Power

 

 

 

 

 

 

 

 

Supply

 

 

 

 

 

 

4

 

 

 

 

 

 

 

 

 

 

Neutral

Hot

 

 

 

3

 

 

 

 

5 Amp Fast Blo fuse

 

 

 

 

 

 

 

 

 

 

Slidewire 100 to 1000

Closed

Wiper

Open

 

 

 

 

 

 

 

 

 

 

 

 

 

mechanically linked

 

 

 

 

 

 

 

 

to motor

 

 

 

 

 

 

 

 

 

 

 

 

Open

Closed

 

 

 

 

 

 

 

 

1

 

 

 

2

 

 

 

Output

N.C.

 

 

 

 

 

 

L1

Relay#1

2

 

 

 

 

 

 

 

 

N.O.

 

 

 

 

 

 

L2/N

 

3

 

 

 

 

 

 

22

 

4

 

 

 

 

 

 

 

Output

N.C.

 

 

 

 

 

 

23

5

 

 

 

 

 

 

Relay#2

 

 

 

 

 

 

 

 

N.O.

 

 

 

 

 

 

24

1

6

 

 

 

 

 

 

 

 

 

 

Connect shield to ground

 

 

25

 

7

 

 

 

at one end only

 

 

 

Alarm

N.C.

Alarm Relay

Load

 

 

 

26

Relay#1

8

#1 Load

 

 

 

 

 

Supply

 

 

 

 

 

N.O.

 

 

 

 

 

 

 

 

 

Power

 

 

 

27

 

9

 

 

 

 

 

 

To terminal

5 Amp Fast Blo fuse

 

 

 

 

 

 

 

 

 

 

 

 

7 or 9

 

 

 

 

 

 

 

 

1Alarm #2 is not available with Position Proportional output or Three Position Step control.

2Do not run slidewire cable in the same conduit as AC power.

3Electrical noise suppression may be required. Refer to Section 12.

4 Slidewire input is not required for Three Position Step control but can be used for motor position indication.