6.4 Entering the Setpoint Program Data

Introduction

The procedure listed in Table 6-1 tells you what keys to press and what

 

prompts you will see when entering the setpoint program data. Follow the

 

prompt hierarchy listed in Table 6-2 when selecting the functions for

 

setpoint programming.

ATTENTION

Make sure SP RAMP and SP RATE are disabled first.

Step

1

Table 6-1

Action

Select SP PROG

Group

Setpoint Program Data Entry Procedure

Press

 

 

 

 

Result

 

 

 

 

 

 

 

 

 

until you see

 

 

SET UP

 

 

 

 

 

Upper Display

 

 

 

 

 

 

 

 

ENABLE

 

 

 

Lower Display

 

ENABL2

 

 

 

 

ENAB12

 

 

 

 

 

 

 

 

 

SP PROG

 

 

 

 

 

 

 

 

 

2

3

4

5

Select the functions

Change the value or selection of a function prompt

Enter value or selection into memory

Exit configuration

or

FUNCTION

LOOP 1/2

or

FUNCTION

LOOP 1/2

LOWER

DISPLAY

to enable the setpoint programming option on Loop 1, Loop 2, or both.

This accesses the function prompts SP Programming.

Upper Display

Shows the current value for each prompt.

Lower Display

The individual function prompts within the setpoint program group are shown.

Successive presses of the [FUNCTION] key will sequentially display all the functions and their values or selections. Follow the prompt hierarchy shown in Table 6-2.

This changes the value or selection in the upper display. If the display blinks, you are trying to select an unacceptable value.

This enters the value or selection and goes to another prompt. Repeat steps 3 and 4 for each function you want to change.

This exits from the configuration mode.

Alarms on the setpoint program

Prompt hierarchy

You can configure an event to go ON or OFF at the beginning or end of any segment. Refer to Section 3 - Configuration under “Alarms Parameters Group” for details.

Table 6-2 lists all the function prompts for Setpoint Program data configuration in the order of their appearance. Follow the procedure in Table 6-1 to transfer the data from your setpoint Ramp/Soak profile into the controller. All parameters may be changed while the program is disabled or in HOLD.