4.11 Loop 1 Control Parameters Set Up Group

Introduction

Control group prompts

Lower Display

Prompt

PV SOURCE

PID SETS

The functions listed in this group deal with how the Single-Loop process controller or Loop 1 of a Two-Loop process controller will control the process including: PV source, Number of tuning parameter sets, Setpoint source, Tracking, Power-up recall, Setpoint limits, Output direction, rate and limits, Power-up preset outputs, Dropoff, Deadband, and Hysteresis.

Table 4-10 lists all the function prompts in the Control Set Up group and their definitions.

 

Table 4-10

Control Group Definitions

 

 

 

 

 

 

 

 

 

 

 

 

Upper Display

 

 

Parameter

 

 

 

Range of Setting

 

 

Definition

 

 

 

or Selection

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PROCESS VARIABLE SOURCE — Select the source of

 

 

 

 

the Process Variable.

 

 

 

 

INP 1

 

INPUT 1

 

 

 

 

INP 2

 

INPUT 2

 

 

 

 

IN AL1

 

INPUT ALGORITHM 1

 

 

 

 

IN AL2

 

INPUT ALGORITHM 2

 

 

 

 

INP 3

 

INPUT 3

 

 

 

 

 

 

 

 

 

 

 

 

 

NUMBER OF TUNING PARAMETER SETS— This

 

 

 

 

selection lets you choose one or two sets of tuning

 

 

 

 

constants (gain, rate, and reset).

 

 

 

1 ONLY

 

ONE SET ONLY— Only one set of tuning parameters is

 

 

 

 

 

 

 

available. Configure the values for:

 

 

 

 

 

 

Gain (proportional band),

 

 

 

 

 

 

Rate,

 

 

 

 

 

 

 

Reset Time, and

 

 

 

 

 

 

 

Cycle Time (if time proportional is used).

 

 

2KEYBD

 

TWO SETS KEYBOARD SELECTABLE— Two sets of

 

 

 

 

 

 

 

tuning parameters can be configured and can be selected

 

 

 

 

at the operator interface or by using the Digital Inputs.

 

 

 

 

 

 

 

 

 

 

 

Press

LOWER DISPLAY

key until you see PID SET1 or

 

 

 

 

PID SET2 then press

or

to switch between

 

 

 

 

sets. Configure the values for:

 

 

 

 

 

 

Gain, Rate, Reset, Cycle Time

 

 

 

 

 

Gain #2, Rate #2, Reset #2, Cycle #2 Time

 

See Subsection 5.10 for procedures.

118

UDC 3300 Process Controller Product Manual

4/00

Page 130
Image 130
Honeywell UDC 3300 manual Introduction Control group prompts Lower Display Prompt, PV Source PID Sets, Input Algorithm