Lower Display

Prompt

Upper Display

Range of Setting

or Selection

Parameter Definition

TOT RATE

SECOND

MINUTE

HOUR

DAY

ML/DAY

TOTALIZER INTEGRATION RATE— Determines the rate at which the Totalizer is updated.

SECOND — Engineering units per second

MINUTE— Engineering units per minute

HOUR— Engineering units per hour

DAY — Engineering units per day

MIL/DAY— Millions of units per day

ATTENTION The source of the Totalizer is averaged over the sample and update rates. For example, since the loop cycle speed is six per second, then with the Totalizer Rate set at once per minute, the source is averaged six times per second and the Totalizer value is updated with this average value ÷ 60 once per second.

NOTE 1: Does not apply to Three Position Step Control.

NOTE 2. If the calculated value of the quantity under the square root sign decreases to a value less than 0.010, the calculation will become linear as the calculated value decreases below 0.010.

*Where: K = 0.001 to 1000 (configurable)

Calc Hi and Calc Lo are configurable over a range of –999 to 9999

108

UDC 3300 Process Controller Product Manual

4/00

Page 120