Honeywell UDC 3300 manual Factory Setting Refer, ALG2 INA, ALG2 INB, ALG2 INC, PCT H2 ALG2 Bias

Models: UDC 3300

1 294
Download 294 pages 16.21 Kb
Page 63
Image 63

Function Prompt

Function

Lower Display

Name

 

 

 

CALC HI

Calculated Variable High

 

Scaling Factor for Input

 

Algorithm 2

 

 

CALC LO

Calculated Variable Low

 

Scaling Factor for Input

 

Algorithm 2

 

 

ALG2 INA

Input Algorithm 2

 

Input A Selection

 

 

ALG2 INB

Input Algorithm 2

 

Input B Selection

 

 

ALG2 INC

Input Algorithm 2

 

Input C Selection

 

 

Selections or

Range of Setting

Upper Display

–999. To 9999. Floating (in engineering units)

–999. To 9999. Floating (in engineering units)

INP 1

IN AL1

INP 2

IN AL2

LP1OUT

INP 3

LP2OUT

 

 

 

INP 1

IN AL1

INP 2

IN AL2

LP1OUT

INP 3

LP2OUT

 

 

 

NONE

LP2OUT

INP 1

IN AL1

INP 2

IN AL2

LP1OUT

INP 3

 

 

Factory Setting

- -

- -

- -

- -

- -

Refer

to

PCT H2

ALG2 BIAS

Hydrogen Content for

1.0 to 99.0 %

Dewpoint

 

 

 

Input Algorithm2 Bias

-999 to 9999 floating (in engineering

 

units)

 

 

1.0

0.000

8SEG CH1*

X0 VALUE

X1 VALUE

X2 VALUE

X3 VALUE

X4 VALUE

X5 VALUE

X6 VALUE

X7 VALUE

X8 VALUE

Y0 VALUE Y1VALUE Y2VALUE Y3VALUE Y4VALUE Y5VALUE Y6VALUE Y7VALUE Y8 VALUE

8SEG CH2*

Eight Segment Characterizer

If Characterizer 1 is enabled, the following Xn VALUE and Yn VALUE parameters appear.

Xn Input Value (X Axis)

(n = 0 through 8)

Yn Output Value (Y Axis)

(n = 0 through 8)

Eight Segment Characterizer 2

If Characterizer 2 is enabled, the following Xn VALU2 and Yn VALU2 parameters appear.

DISABL

INPUT1

INPUT2

L1 OUT

L2 OUT

0 to 99.99 %

0 to 99.99 %

DISABL

INPUT1

INPUT2

L1 OUT

L2 OUT

DISABL

0

0

DISABL

4/00

UDC 3300 Process Controller Product Manual

51

Page 63
Image 63