Table 4-5 Algorithm Group Definitions, Continued

Lower Display

Prompt

Upper Display

Range of Setting

or Selection

Parameter Definition

 

8SEG CH1

 

8 SEGMENT CHARACTERIZER #1— An eight segment

 

 

 

 

characterizer can be applied to either Input 1, Input 2,

 

 

 

 

Output 1, or Output 2.

 

 

 

DISABL

DISABLE— Disables characterizer.

 

 

 

INPUT1

INPUT 1— Characterizer is applied to Input 1.

 

 

 

INPUT2

INPUT 2— Characterizer is applied to Input 2.

 

 

 

L1 OUT

LOOP 1 OUTPUT— Characterizer is applied to Loop 1

 

 

 

 

Output. (NOTE 1)

 

 

 

L2 OUT

LOOP 2 OUTPUT— Characterizer is applied to Loop 2

 

 

 

 

Output.

 

 

 

 

There are eight (Xn) Input values and eight (Yn) Output

 

 

 

 

values to be selected. The following rules apply:

 

 

 

 

• When Input 2 is used, Input 2 Ratio and Bias are

 

 

 

 

applied to the Xn Values.

 

 

 

 

• When one of the Loop outputs are selected, the Xn

 

 

 

 

Input values are the Output from the control algorithm,

 

 

 

 

and the Yn Output is the final control element action.

 

 

 

 

This application is useful for non-linear control elements

 

 

 

 

or Process Variable.

 

 

 

 

A simple example is shown in Figure 4-2.

 

 

 

 

 

 

 

 

 

 

ATTENTION The X values below should be entered as increasing values (from 0% to 100%) from N = 0 to 8.

X0 VALUE

0.00 to 99.99 %

X0 INPUT VALUE (X AXIS)

X1 VALUE

0.00 to 99.99 %

X1 INPUT VALUE (X AXIS)

X2 VALUE

0.00 to 99.99 %

X2 INPUT VALUE (X AXIS)

X3 VALUE

0.00 to 99.99 %

X3 INPUT VALUE (X AXIS)

X4 VALUE

0.00 to 99.99 %

X4 INPUT VALUE (X AXIS)

X5 VALUE

0.00 to 99.99 %

X5 INPUT VALUE (X AXIS)

X6 VALUE

0.00 to 99.99 %

X6 INPUT VALUE (X AXIS)

X7 VALUE

0.00 to 99.99 %

X7 INPUT VALUE (X AXIS)

X8 VALUE

0.00 to 99.99 %

X8 INPUT VALUE (X AXIS)

Y0 VALUE

0.00 to 99.99 %

Y0 INPUT VALUE (Y AXIS)

Y1 VALUE

0.00 to 99.99 %

Y1 INPUT VALUE (Y AXIS)

Y2 VALUE

0.00 to 99.99 %

Y2 INPUT VALUE (Y AXIS)

Y3 VALUE

0.00 to 99.99 %

Y3 INPUT VALUE (Y AXIS)

Y4 VALUE

0.00 to 99.99 %

Y4 INPUT VALUE (Y AXIS)

Y5 VALUE

0.00 to 99.99 %

Y5 INPUT VALUE (Y AXIS)

Y6 VALUE

0.00 to 99.99 %

Y6 INPUT VALUE (Y AXIS)

Y7 VALUE

0.00 to 99.99 %

Y7 INPUT VALUE (Y AXIS)

Y8 VALUE

0.00 to 99.99 %

Y8 INPUT VALUE (Y AXIS)