4.10 Input 3 Parameters Set Up Group

Introduction

Input 3 group prompts

Lower Display

Prompt

These are the parameters required for Input 3: actuation, transmitter characterization, high and low range values in engineering units, ratio, bias, and filter.

ATTENTION Input 3 prompts appear on expanded models only. Prompts for Input 3 only appear if Input 2 PWA is installed and the actuation for Input 2 is configured for one of the following types: 0-5 Vdc, 1-5 Vdc, 0-20 mA, or 4-20 mA.

Table 4-9 lists all the function prompts in the Input 3 Set Up group and their definitions.

Table 4-9

Input 3 Group Definitions

 

 

 

Upper Display

 

Parameter

Range of Setting

 

Definition

or Selection

 

 

 

 

 

IN3 TYPE

ATTENTION

Changing the input type will result in the loss of Field Calibration values and will restore Factory Calibration values.

XMITTER2

IN3 HI

IN3 LO

RATIO 3

BIAS IN3

FILTER 3

DISABL 0-20mA 4-20mA 0-5 V 1-5 V

Input 3 ranges and selections are same as for Input 1 except Burnout and Emissivity are not available.

INPUT 3 ACTUATION TYPE – This selection determines what actuation you are going to use for Input 3.

DISABL— Disables Input 3

0-20mA 0 to 20 milliamperes

4-20mA 4 to 20 milliamperes

0-5 V— 0 to 5 volts

1-5 V— 1 to 5 volts

Refer to Input 1 parameters for definitions.

4/00

UDC 3300 Process Controller Product Manual

117

Page 129
Image 129