Lower Display

Upper Display

 

Prompt

Range of Setting

 

 

 

or Selection

 

 

 

 

 

INP ALG2

NONE

 

 

 

W AVG

 

ATTENTION

 

F FWR2

 

• All Input Algorithms

 

FFWDM2

 

operate in engineering

A-B/C*

 

units except Feed-

HI SEL

 

forward which operates

LO SEL

 

in percent of range units.

MuDIV

 

• For General Math

MULT

 

functions, when Input C

 

MuDIV

 

is disabled, the value of

 

MULT

 

Input C used in the

 

DEW PT

 

functions is

 

 

 

automatically set to 1.0.

 

 

 

 

 

MATH K2

0.001 to 1000 floating

 

 

 

 

CALC HI

–999. To 9999. Floating

 

 

 

(in engineering units)

 

 

 

 

CALC LO

–999. To 9999. Floating

 

 

 

(in engineering units)

 

 

 

 

ALG2 INA

 

 

 

 

INP 1

 

 

 

INP 2

 

 

 

LP1OUT

 

 

 

LP2OUT

 

 

 

IN AL1

 

 

 

IN AL2

 

 

 

INP 3

 

 

 

 

ALG2 INB

 

 

 

 

INP 1

 

 

 

INP 2

 

 

 

LP1OUT

 

 

 

LP2OUT

 

 

 

IN AL1

 

 

 

IN AL2

 

 

 

INP 3

 

 

 

 

ALG2 INC

 

 

 

 

NONE

 

 

 

INP 1

 

 

 

INP 2

 

 

 

LP1OUT

 

 

 

LP2OUT

 

 

 

IN AL1

 

 

 

IN AL2

 

 

 

INP 3

 

 

 

 

Parameter

Definition

INPUT ALGORITHM 2— The selections from which to choose are listed to the left.

The formulas are the same as shown for IN ALG 1.

*ATTENTION Selection A–B/Calgorithm subtracts Input B with Ratio/Bias from Input A with Ratio/Bias and divides the result by Input C with Ratio/Bias using engineering units.

EXAMPLE:

PV or SP = K (A–B) (Calc Hi – Calc Lo)

C

WEIGHTED AVERAGE RATIO OR MASS FLOW ORIFICE CONSTANT (K) FOR MATH SELECTIONS— Only applicable for algorithm W AVG or General Math selections MuDIV, MULT, MuDIV, or MULT.

CALCULATED VARIABLE HIGH SCALING FACTOR FOR INPUT ALGORITHM 2— Does not apply to Feedforward algorithms. Range is used for either PV or RSP, depending upon Algorithm application.

CALCULATED VARIABLE LOW SCALING FACTOR FOR INPUT ALGORITHM 2— Does not apply to Feedforward algorithms. Range is used for either PV or RSP, depending upon Algorithm application.

ALGORITHM 2, INPUT A SELECTION will represent one of the available selections.

Input 1

Input 2

Output 1 (NOTE 1)

Output 2

Input Algorithm 1

Input Algorithm 2

Input 3

ALGORITHM 2, INPUT B SELECTION will represent one of the available selections.

Input 1

Input 2

Output 1 (NOTE 1)

Output 2

Input Algorithm 1

Input Algorithm 2

Input 3

ALGORITHM 2, INPUT C SELECTION will represent one of the available selections.

None

Input 1

Input 2

Output 1 (NOTE 1)

Output 2

Input Algorithm 1

Input Algorithm 2

Input 3