Function Prompt

Lower Display

OUT RATE

PCT/M UP

PCT/M DN

OUTHiLIM

OUTLoLIM

IHiLIM I LoLIM

DROPOFF

DEADBAND

FAILMODE

FAILSAFE

Function

Name

Output Change Rate

Output Rate Up Value

Output Rate Down Value

High Output Limit

Low Output Limit

High Reset Limit

Low Reset Limit

Controller Dropoff Value

Output Relay Deadband

Failsafe Mode

Failsafe Output Value

Selections or

Range of Setting

Upper Display

ENABLE

DISABL

0 to 9999 % per minute

0 to 9999 % per minute

–5 to 105 % of output

–5 to 105 % of output

Within the range of the output limits

Within the range of the output limits

–5 to 105 % of output

–5.0 to 5.0 %

NO LAT

LATCH

Set within the range of the output limits. 0 to 100 %

Factory

Refer

Setting

to

 

 

DISABL

Section

4.12

0

0

100

0

100.0

0.0

0

1.0

NO LAT

0