Lower Display

Prompt

ALG1 INA

ALG1 INB

ALG1 INC

PCO SEL

PCT CO

ATM PRES

ALG1 BIAS

Upper Display

Range of Setting

or Selection

INP 1

INP 2

LP1OUT

LP2OUT

IN AL1

IN AL2

INP 3

INP 1

INP 2

LP1OUT

LP2OUT

IN AL1

IN AL2

INP 3

NONE

INP 1

INP 2

LP1OUT

LP2OUT

IN AL1

IN AL2

INP 3

DISABL

ONLINE

0.020 to 0.350 (fractional percent of CO)

590.0 to 760.0 (mm Hg)

-999 to 9999 floating (in engineering units)

Parameter

Definition

ALGORITHM 1, INPUT A SELECTION will represent one of the available selections.

Input 1

Input 2

Output 1 (NOTE 1)

Output 2

Input Algorithm 1

Input Algorithm 2

Input 3

ALGORITHM 1, INPUT B SELECTION will represent one of the available selections.

Input 1

Input 2

Output 1 (NOTE 1)

Output 2

Input Algorithm 1

Input Algorithm 2

Input 3

ALGORITHM 1, INPUT C SELECTION will represent one of the available selections.

None

Input 1

Input 2

Output 1 (NOTE 1)

Output 2

Input Algorithm 1

Input Algorithm 2

Input 3

PERCENT CARBON SOURCE allows a live Input 3 value to be substituted for the static % CO value (PCT CO).

DISABLED

ONLINE— Input 3 must be enabled

PERCENT CARBON is only applicable when Carbon Potential is selected. Enter the value in percent carbon monoxide that is applicable for the enriching gas used in fractional form.

FOR EXAMPLE:

Natural Gas = 20.0 % CO, then setting is 0.200 Propane Gas = 23.0 % CO, setting is 0.230

ATMOSPHERIC PRESSURE COMPENSATION is only applicable when Relative Humidity is selected. Enter the value of the atmospheric pressure of the process.

INPUT ALGORITHM 1 BIAS—Does not apply to selections: FFWRD, FFWDM2, HISEL, or LOSEL.

4/00

UDC 3300 Process Controller Product Manual

99

Page 111
Image 111
Honeywell UDC 3300 manual INP LP1OUT LP2OUT AL1 AL2 None Disabl Online, Disabled, For Example