Current output/ universal output connections

Figure 2-12 shows the Output and Alarm wiring connections for models

with Current Output (Model DC330X-KE-XXXand Model

DC330X-C0-XXX). See Table 2-5 for wiring restrictions.

For Control and Alarm Relay Contact information, see Tables 2-7 and 2-8.

Figure 2-12 Current Output—Current /Time Duplex, Time/Current Duplex, Position Proportional,

or Three Position Step Control

 

 

 

 

See Table 2-7 for relay

 

 

 

 

terminal connections for

 

10

1

 

Output Algorithm selected.

 

+

 

 

L1

11

2

 

 

Current Output

Controller Load

 

L2/N

 

3

4–20 mA

0–1000 Ohms

 

 

 

22

 

4

 

 

Output#1

 

 

 

 

or

N.C.

Output or Alarm

Load

23

5

Alarm#2

Relay 2 Load

Supply

 

N.O

24

Relay

6

To terminal

 

Power

 

1

 

 

 

4 or 6

 

25

Output#2

7

 

 

 

 

 

26

or

N.C.

Output or Alarm

Load

Alarm#1

8

Relay 3 Load

Supply

 

Relay

N.O.

27

 

 

Power

 

9

To terminal

1

 

 

 

7 or 9

 

 

 

 

 

 

For Duplex Current Output use Auxiliary Output for Output 2 (cool) (see Figure 2-14).

ATTENTION:

All current outputs are isolated from each other, case ground, and all inputs.

1Electromechanical relays are rated at 5 Amps @120 Vac or 2.5 Amps at 240 Vac. Customer should size fuses accordingly. Use Fast Blo fuses only.

Relays are NOT available on DC330X-C0-XXX.

24167

 

 

 

Table 2-5 Universal Output Wiring Functionality and Restrictions for Figure 2-12

Controller with Two Current Outputs and Two Relay Outputs

SINGLE LOOP OR CASCADE CONTROL OUTPUT

Output Type

Time Simplex

Current

Position (not available on Cascade Control)

Time Duplex or TPSC

Current Duplex 100%

Current Duplex 50%

Current/Time or

Time/Current

Current

Not used

Output 1

Not used

Not used

Output 1

Output 1

Output 1 or 2

Auxiliary

Not used

Not used

Not used

Not used

Not used

Output 2

Not used

Relay #1

N/A

N/A

N/A

N/A

N/A

N/A

N/A

Relay #2

Output 1

Alarm 2

Output 1

Output 1

Alarm 2

Alarm 2

Output 1 or 2

Relay #3

Alarm 1

Alarm 1

Output 2

Output 2

Alarm 1

Alarm 1

Alarm 1

26

UDC 3300 Controller Product Manual

4/00

Page 38
Image 38
Honeywell UDC 3300 manual Current output/ universal output connections, Controller Load L2/N, Ohms, Output or Alarm Load