3.12Input 1 Parameters Set Up Group

Introduction

Function prompts

This data deals with various parameters required to configure Input 1.

Table 3-9 lists all the function prompts in the Input 1 Set Up group.

Function Prompt

Lower Display

IN1 TYPE

XMITTER1

Table 3-9 Input 1 Group Function Prompts

Function

 

Selections or

Name

 

Range of Setting

 

 

Upper Display

 

 

 

Input 1 Actuation Type

DISABL

W TC H

 

B TC

W TC L

 

E TC H

100 PT

 

E TC L

100 LO

 

J TC H

200 PT

 

J TC L

500 PT

 

K TC H

RAD RH

 

K TC L

RAD RI

 

NNM H

0-20mA

 

NNM L

4-20mA

 

NM90 H

0-10mV

 

NM90 L

0-50mV

 

NIC TC

0-5 V

 

R TC

1-5 V

 

S TC

0-10 V

 

T TC H

CARBON

 

T TC L

OXYGEN

Transmitter Characterization

B TC

S TC

 

E TC H

T TC H

 

E TC L

T TC L

 

J TC H

W TC H

 

J TC L

W TC L

 

K TC H

100 PT

 

K TC L

100 LO

 

NNM H

200 PT

 

NNM L

500 PT

 

NM90 H

RAD RH

 

NM90 L

RAD RI

 

NIC TC

LINEAR

 

R TC

SQROOT

 

 

ANALYT*

Factory Setting

0-10mV

LINEAR

Refer

to

Section

4.8

ANALYTIC*

IN1 HI

IN1 LO

RATIO 1

Analytic Selections

XMITTER1 must be set to ANALYT for this prompt to appear

Input 1 High Range Value (Linear Inputs only)

Input 1 Low Range Value (Linear Inputs only)

Input 1 Ratio

NONE

PH

ORP mV

CONDmS

CONDuS

RSTVM^

TDS PPm

TDS PPb

CONCPt

DO PPm

DO PPb

–999. To 9999. Floating (in engineering units)

–999. to 9999. floating (in engineering units)

–20.00 to 20.00

(floats to 3 decimal places)

NONE

1000

0

1.000

54

UDC 3300 Process Controller Product Manual

4/00

Page 66
Image 66
Honeywell UDC 3300 manual Input 1 Parameters Set Up Group, Input 1 Group Function Prompts Selections or, IN1 Type XMITTER1