highlight bar to the Current Sensor Zero Offset Calibration and press the Enter button. The following confirmation screen will be displayed:

Figure 57 – DCR100 Current Sensor Zero Offset Calibration Screen

Press Begin to execute the calibration process or Cancel to return to the previous menu. During the calibration process, all channels will be turned off. When the calibration is complete, the following screen will be displayed.

Figure 58 – DCR100 Current Sensor Zero Offset Calibration Completion Screen

Press the Back button to return to the previous menu.

6.6.1.2 Device Instance

This entry allows you to program the NMEA 2000 device instance for the unit. You usually will not need to modify the default value of “0”.