Total Access 600 Series System Manual

Section 3 Network Turnup Procedure

 

 

Contents of ADTRAN Shipments

Your ADTRAN shipment includes the following items:

The Total Access 6XX unit with attached wallmount brackets

The Total Access 600 Series System CD – ADTRAN P/N 3253052

Hardware revision notice card – ADTRAN P/N 61200624L1-17

Mounting instructions – ADTRAN P/N 61200624L1-19

RJ-45 to RJ-45 8-pin cable (6 ft) –ADTRAN P/N 3127004

Cable tie (for securing attached cables) – ADTRAN P/N 3292032

Four rubber feet (for table top installations) – ADTRAN P/N 3270BF003

3-prong, detachable power cord – ADTRAN P/N 3127009

Customer must supply Ethernet cable and the RJ-48 to DB-9 adapter and DB-9 serial cable for configuration via the VT100 CRAFT interface.

4.GROUNDING INSTRUCTIONS

To following paragraphs provide grounding instruction information from the Underwriters’ Laboratory UL60950 Standard for Safety of Information Technology Equipment Including Electrical Business Equipment, with revisions dated March 15, 2002.

An equipment grounding conductor that is not smaller in size than the ungrounded branch-circuit supply conductors is to be installed as part of the circuit that supplies the product or system. Bare, covered, or insulated grounding conductors are acceptable. Individually covered or insulated equipment grounding conductors shall have a continuous outer finish that is either green, or green with one or more yellow stripes. The equipment grounding conductor is to be connected to ground at the service equipment.

The attachment-plug receptacles in the vicinity of the product or system are all to be of a grounding type, and the equipment grounding conductors serving these receptacles are to be connected to earth ground at the service equipment.

A supplementary equipment grounding conductor shall be installed between the product or system and ground that is in addition to the equipment grounding conductor in the power supply cord.

The supplementary equipment grounding conductor shall not be smaller in size than the ungrounded branch-circuit supply conductors. The supplementary equipment grounding conductor shall be connected to the product at the terminal provided, and shall be connected to ground in a manner that will retain the ground connection when the product is unplugged from the receptacle. The connection to ground of the supplementary equipment grounding conductor shall be in compliance with the rules for terminating bonding jumpers at Part K or Article 250 of the National Electrical Code, ANSI/NFPA 70. Termination of the supplementary equipment grounding conductor is permitted to be made to building steel, to a metal electrical raceway system, or to any grounded item that is permanently and reliably connected to the electrical service equipment ground.

The supplemental grounding conductor shall be connected to the equipment using a number 8 ring terminal and should be fastened to the grounding lug provided on the rear panel of the equipment. The ring terminal should be installed using the appropriate crimping tool (AMP P/N 59250 T-EAD Crimping Tool or equivalent).

61200624L1-1B

© 2004 ADTRAN, Inc.

37

Page 39