Chapter 5 Trial Run and Tuning ProcedureASDA-B Series

Table 5.B P2-31 Value in AutoMode(PDFF) and the setting of Speed Loop Responsiveness.

Setting Value of

Speed Loop Responsiveness

P2-31

 

0

10 Hz

 

 

1

15 Hz

 

 

2

20 Hz

 

 

3

25 Hz

 

 

4

30 Hz

 

 

5

35 Hz

 

 

6

45 Hz

 

 

7

55 Hz

 

 

Setting Value of

Speed Loop Responsiveness

P2-31

 

8

65 Hz

 

 

9

80 Hz

 

 

A

100 Hz

 

 

B

120 Hz

 

 

C

145 Hz

 

 

D

170 Hz

 

 

E

260 Hz

 

 

F

300 Hz

 

 

5.5.5 Limit of Load Inertia Estimation

1.The accel. / decel. time for reaching 2000RPM must be below 1 second. The rotation speed must be above 200RPM. The load inertia must be 100 multiple or less of motor inertia. The change of external force and the inertia ratio can not be too much.

2.The measured load inertia value will not be saved when the power is cut off. When re-apply the power to the drive every time, the setting value of P1-37 is equal to the initial value of load inertia value. But, when the Tuning Mode Settings of P2-32 is set from AutoMode #1 to AutoMode #2, the measured inertia value will be memorized in P1-37 automatically.

5-18

Revision January 2009