Chapter 7 Servo ParametersASDA-B Series

Setting value of P2-10 ~ P2-15: 05

DI Name

 

 

 

 

 

DI Function Description

 

 

 

 

Trigger Method

Control

 

 

 

 

 

 

 

 

 

Mode

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Zero speed CLAMP. When ZCLAMP is activated (ON) and

 

 

 

 

the motor speed value is below the setting value of P1-38, it

 

 

 

 

is used to lock the motor in the instant position.

 

 

 

 

Speed

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Command

 

 

 

 

 

 

 

 

 

 

 

 

Setting value of

 

 

 

 

 

 

 

 

 

 

ZCLAMP

 

P1-38 (Zero speed)

 

 

 

 

 

 

 

 

 

 

Level Triggered

S

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ZCLAMP

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

input signal

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

 

ON

 

 

 

 

 

Motor Speed

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Setting value of

 

 

 

 

 

 

 

 

 

 

 

 

P1-38 (Zero speed)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Time

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Setting value of P2-10 ~ P2-15: 06

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DI Name

 

 

 

 

 

DI Function Description

 

 

 

 

Trigger Method

Control

 

 

 

 

 

 

 

 

 

Mode

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CMDINV

 

Command input reverse control. When the drive is in the

Level

S, T

 

Position, Speed and Torque mode, and CMDINV is

 

Triggered

 

 

activated, the motor is in reverse rotation.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Setting value of P2-10 ~ P2-15: 07

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DI Name

 

 

 

 

 

DI Function Description

 

 

 

 

Trigger Method

Control

 

 

 

 

 

 

 

 

 

Mode

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Pulse inhibit input. When the drive is in position mode, if

Level

P

INHP

 

INHP is activated, the external pulse input command is not

 

Triggered

 

 

valid.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Setting value of P2-10 ~ P2-15: 08

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DI Name

 

 

 

 

 

DI Function Description

 

 

 

 

Trigger Method

Control

 

 

 

 

 

 

 

 

 

Mode

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Reserved

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Setting value of P2-10 ~ P2-15: 09

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DI Name

 

 

 

 

 

DI Function Description

 

 

 

 

Trigger Method

Control

 

 

 

 

 

 

 

 

 

Mode

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Torque limit enabled. When the drive is in speed and

 

 

TRQLM

 

position mode, and TRQLM is activated, it indicates the

Level

P, S

 

torque limit command is valid. The torque limit command

Triggered

 

 

 

 

 

source is internal parameter or analog voltage.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Revision January, 2009

7-75