Chapter 6 Control Modes of OperationASDA-B Series

Settings:

It is used to determine the acceleration time to accelerate from 0 to its rated rotation speed. (When P1-36 is set to 0: Accel/Decel function is disabled, i.e. P1-34, P1-35 is disabled)

P1 - 35

TDEC

Deceleration Time

Communication Addr.: 0123H

 

 

 

Default: 200

Related Section:

Applicable Control Mode: S

P1-34, P1-36, Section 6.3.3

Unit: ms

 

 

Range: 1 ~ 20000

Settings:

It is used to determine the deceleration time to decelerate from its rated rotation speed to 0. (When P1-36 is set to 0: Accel/Decel function is disabled, i.e. P1-34, P1-35 is disabled)

P1 - 36

TSL

Accel /Decel S-curve

Communication Addr.: 0124H

 

 

 

Default: 0

 

Related Section:

Applicable Control Mode: S

P1-34, P1-35, Section 6.3.3

Unit: ms

 

 

Range: 0 ~ 10000 (0: Disabled)

Settings:

This parameter is used to make the motor run more smoothly when startup and windup.

Using this parameter can improve the motor running stability.

Speed

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Time

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(ms)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TSL/2 TACC

TSL/2

TSL/2

TDEC

TSL/2

TSL: P1-36, Accel /Decel S-curve

 

Total acceleration time = TACC + TSL

TACC: P1-34, Acceleration time

 

Total deceleration time = TDEC + TSL

TDEC: P1-35, Deceleration time

 

 

 

 

 

 

 

 

 

NOTE

1)If the setting value of parameter P1-36 is set to 0, it indicates Accel / Decel S-curve function is disabled and the command is just By-Pass.