Chapter 7 Servo ParametersASDA-B Series

SOF1

Analog Speed Input Drift Adjustment 1

Communication Addr.: 040BH

 

 

 

Default: Factory setting

Related Section:

Applicable Control Mode: P/S/T

P4-10

Unit: N/A

 

 

Range: 0 ~ 32767

Settings:

Manual Adjustment Operation:

Set parameter P2-08 to 22 and then change this parameter. This is an auxiliary adjusting function, although this parameter allows the users can execute manual adjustment, we still do not recommend users to change the default setting manually.

Auto Adjustment Operation:

Set parameter P2-08 to 20 first and then set parameter P4-10 to 1.

When executing this auto adjustment, ensure that the external wiring connected to analog speed must be removed or an external zero voltage power is applied to the servo drive from the host controller and the servo system should be off (Servo off).

NOTE

1) When P2-08 is set to 10, users cannot reset this parameter.

P4 - 12

SOF2

Analog Speed Input Drift Adjustment 2

Communication Addr.: 040CH

 

 

 

Default: Factory setting

Related Section:

Applicable Control Mode: P/S/T

P4-10

Unit: N/A

 

 

Range: 0 ~ 32767

Settings:

Please see P4-11 for explanation.

NOTE

1) When P2-08 is set to 10, users cannot reset this parameter.

P4 - 13

TOF1

Analog Torque Drift Adjustment 1

Communication Addr.: 040DH

 

 

 

Default: Factory setting

Related Section:

Applicable Control Mode: P/S/T

P4-10

Unit: N/A

 

 

Range: 0 ~ 32767

Settings:

Manual Adjustment Operation:

Set parameter P2-08 to 22 and then change this parameter. This is an auxiliary adjusting