Delta Electronics ASDA-B Series manual Flt, Transmission Fault Treatment Communication Addr H, Cwd

Models: ASDA-B Series

1 321
Download 321 pages 45.58 Kb
Page 210
Image 210

P3 - 02

 

 

Chapter 7 Servo ParametersASDA-B Series

 

 

 

 

 

PTL

Communication Protocol

 

Communication Addr.: 0302H

 

 

 

 

 

 

Default: 0

 

 

Related Section:

Applicable Control Mode: P/S/T

 

Section 8.2

Unit: N/A

 

 

 

 

Range: 0 ~ 8

Settings:

0:Modbus ASCII mode, <7,N,2>

1:Modbus ASCII mode, <7,E,1 >

2:Modbus ASCII mode, <7,O,1>

3:Modbus ASCII mode, <8,N,2 >

4:Modbus ASCII mode, <8,E,1>

5:Modbus ASCII mode, <8,O,1>

6:Modbus RTU mode, <8,N,2>

7:Modbus RTU mode, <8,E,1>

8:Modbus RTU mode, <8,O,1>

This parameter is used to set the communication protocol. The alphanumeric characters represent the following: 7 or 8 is the number of data bits; N, E or O refer to the parity bit, Non, Even or Odd; the 1 or 2 is the numbers of stop bits.

P3 - 03

FLT

Transmission Fault Treatment

Communication Addr.: 0303H

 

 

 

Default: 0

 

Related Section:

Applicable Control Mode: P/S/T

Section 8.2

Unit: N/A

 

 

Range: 0 ~ 1

Settings:

0:Display fault and continue operating

1:Display fault and stop operating

This parameter is used to determine the operating sequence once a communication fault has been detected. If '1' is selected the drive will stop operating upon detection the communication fault. The mode of stopping is set by parameter P1-32.

P3 - 04

CWD

Communication Time Out Detection

Communication Addr.: 0304H

 

 

 

Default: 0

 

Related Section:

Applicable Control Mode: P/S/T

Section 8.2

Unit: N/A

 

 

Range: 0 ~ 20

 

Revision January, 2009

7-57

Page 210
Image 210
Delta Electronics ASDA-B Series manual Flt, Transmission Fault Treatment Communication Addr H, Cwd