Chapter 5 Trial Run and Tuning ProcedureASDA-B Series

Tuning Procedure

13.Pressing UP key is forward rotation and pressing DOWN key is reverse rotation.

14.Execute JOG operation in low speed first. After the machine is running smoothly, then execute JOG operation in high speed.

15.The ratio of Load Inertia to Servo Motor Inertia (J_load /J_motor) cannot be shown in the display of JOG parameter P4-05 operation. Please press MODE key twice continuously and the users can see the ratio of Load Inertia to Servo Motor Inertia (J_load /J_motor). Then, execute JOG operation again, press MODE key once and press SET key twice to view the display on the keypad. Check if the value of J_load /J_motor is adjusted to a fixed value and displayed on the keypad after acceleration and deceleration repeatedly.

„ASD-PU-01B

Estimate the ratio of Load Inertia to Servo Motor Inertia (J_load /J_motor): JOG Mode

Tuning Procedure

Display Message

 

 

1. After wiring is completed, when power in connected to the AC servo drive, the right side display will show on the LED display.

2. Press MODE key to enter into parameter mode.

3. Press SHIFT key twice to select parameter group.

4. Press UP key to view each parameter and select parameter P2-13.

5. Use UP and DOWN key to cycle through the available settings. Then, press SET key to set the setting value of parameter P2-13 as shown on the right side display (Set DI Enabled Status to “Normally open” status).

6. Repeat the action of 4 and 5. Set the setting value of parameter P2- 14 as shown on the right side display.

7. Repeat the action of 4 and 5. Set the setting value of parameter P2- 15 as shown on the right side display.

8. Press MODE key to enter into Monitor mode.

9. Press DOWN key twice to select the ratio of Load Inertia to Servo Motor Inertia (J_load /J_motor).

10. Press FUNC key on the keypad to enter into JOG mode, and the right side display will show on the LED display

11. The default JOG speed value is 20rpm. The users can press UP and DOWN key to increase and decrease JOG speed. Press SHIFT key one time can add one digit number. Adjust JOG speed as 200rpm shown on the right side display.

12. After select desired JOG speed, press SET key and the right side display show on the LCD display.

5-12

Revision January 2009