3-3 Output Signal Description

3-3-2 General-purpose output (DO0 to DO4)

These general-purpose outputs are available to users for freely controlling on/off operation in a pro- gram.

These outputs are used in combination with an external 24V power supply, to drive loads such as solenoid valves and LED lamps. These outputs of course, can be directly connected to a PLC input circuit.

All general-purpose outputs are reset (turned off) when the SRCP controller is turned on or the program is reset.

*When PRM33 ("Operation at return-to-origin complete" parameter) is set to 1 or 3, DO4 does not turn off even if the program is reset. Similarly, when PRM46 ("Servo status output" param- eter) is set to 1, DO3 does not turn off even if the program is reset.

General-purpose output (DO0 to DO4) can be used to perform the following specific functions by parameter setting.

Function name

Parameter

Usable general-purpose input

Alarm output

PRM32 (Alarm number output)

DO0 to DO4

 

 

 

Return-to-origin complete output

PRM33 (Operation at return-to-origin complete)

DO4

 

 

 

Servo-ON status output

PRM46 (Servo status)

DO3

 

 

 

Zone output

PRM53 (Zone output)

DO0 to 3

 

 

 

For more details, see "5-2 Parameter Description".

3-3-3 Feedback pulse output (PA±, PB±, PZ±, PZM±)

This outputs current position data as differential output.

Relation between pulse output and phase

Output pin

CW direction

CCW direction

 

 

 

A17:PA+

B17:PA-

A18:PB+

B18:PB-

A19:PZ+

B19:PZ-

Number of output pulses and Z-phase timing

Number of output pulses*

Z-phase output timing

1 [pulses/m]

Every 1024 m

 

 

*: Number of output pulses is a count after being multiplied by 4.

ZM phase

The ZM phase is output at the magnetic pole detection points of the PHASER series. Refer to the drawing below.

PHASER series

ZM phase

Magnetic pole detection point

3

INTERFACE I/O

3-9