5. PARAMETERS
5.3 Analog output
The servo status can be output to two channels in terms of voltage. Use this function when using an ammeter to monitor the servo status or synchronizing the torque/speed with the other servo.
(1)Setting
Change the following digits of parameter No.22:
Parameter No. 22
0
0
Analog monitor ch2 output selection (Signal output to across
Analog monitor ch1 output selection (Signal output to across
Parameters No.27 and 28 can be used to set the offset voltages to the analog output voltages. The setting range is between 999 and 999mV.
Parameter No. | Description | Setting range [mV] | ||
27 | Used to set the offset voltage for the analog monitor ch1 output. |
|
| 999 to 999 |
28 | Used to set the offset voltage for the analog monitor ch2 output. |
|
| |
|
| |||
|
|
|