12.OPTIONS AND AUXILIARY EQUIPMENT
(2)Selection example
Indicated below is an example of selecting a leakage current breaker under the following conditions:
NV
2mm25m2mm25m
Servo amplifier
SM Servo motor
|
|
|
|
|
|
|
|
|
|
|
|
Ig1 | Iga | Ig2 | Igm |
Use a leakage current breaker generally available.
Find the terms of Equation (12.2) from the diagram:
Ig1 |
| 20 | 5 |
|
| 0.1 [mA] |
|
|
|
| |||
| 1000 | |||||
|
| |||||
Ig2 |
| 20 | 5 |
|
| 0.1 [mA] |
|
|
|
| |||
| 1000 |
|
| |||
|
|
|
Ign 0 (not used)
Iga 0.1 [mA]
Igm 0.1 [mA]
Insert these values in Equation (12.2):
Ig 10 {0.100.13 (0.10.1)}
8.0 [mA]
According to the result of calculation, use a leakage current breaker having the rated sensitivity current (Ig) of 8.0[mA] or more. A leakage current breaker having Ig of 15[mA] is used with the NV- CA/CS/SS series.
12 - 34