12. OPTIONS AND AUXILIARY EQUIPMENT

12.2.7 Leakage current breaker

(1)Selection method

High-frequency chopper currents controlled by pulse width modulation flow in the AC servo circuits. Leakage currents containing harmonic contents are larger than those of the motor which is run with a commercial power supply.

Select a leakage current breaker according to the following formula, and ground the servo amplifier, servo motor, etc. securely.

Make the input and output cables as short as possible, and also make the grounding cable as long as possible (about 30cm (11.8 in)) to minimize leakage currents.

Rated sensitivity current

 

 

10 {Ig1

Ign Iga K

(Ig2

Igm)} [mA] ..........(12.2)

 

 

 

 

Cable

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

K: Constant considering the harmonic contents

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Leakage current breaker

 

 

 

 

NV

 

 

 

 

Noise

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Type

Mitsubishi

K

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

products

 

 

 

 

 

 

 

 

 

 

filter

 

 

 

 

 

 

 

 

 

 

 

 

 

Cable

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Servo

 

 

 

SM

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Models provided with

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

amplifier

 

 

 

 

 

 

 

 

 

NV-SF

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

harmonic and surge

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NV-CF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

reduction techniques

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NV-CA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Ig1 Ign

 

 

 

Iga

 

 

Ig2

 

Igm

 

General models

NV-CS

3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NV-SS

 

Ig1:

Leakage current on the electric channel from the leakage current breaker to the input terminals

 

of the servo amplifier (Found from Fig. 12.1.)

 

 

 

 

Ig2:

Leakage current on the electric channel from the output terminals of the servo amplifier to the

 

servo motor (Found from Fig. 12.1.)

 

 

 

 

 

 

 

 

 

 

 

 

Ign:

Leakage current when a filter is connected to the input side (4.4mA per one FR-BIF)

 

Iga:

Leakage current of the servo amplifier (Found from Table 12.6.)

 

 

Igm:

Leakage current of the servo motor (Found from Table 12.5.)

 

 

 

120

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

current

100

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

80

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Leakage

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

60

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

40

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

[mA] 20

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3.5

8 1422 38 80 150

 

2

 

 

 

 

 

 

 

5.5

30 60 100

Cable size[mm2]

Fig. 12.1 Leakage current example (Ig1, Ig2) for CV cable run in metal conduit

Table 12.5 Servo motor's

 

leakage current

 

example (Igm)

Servo motor

 

Leakage

output [kW]

 

current [mA]

0.05 to 0.5

 

0.1

0.6 to 1.0

 

0.1

1.2 to 2.2

 

0.2

3 to 3.5

 

0.3

5

 

0.5

7

 

0.7

Table 12.6 Servo amplifier's leakage current example (Iga)

Servo amplifier

Leakage current

 

capacity [kW]

 

[mA]

 

 

0.1 to 0.6

 

0.1

 

 

 

 

 

 

 

 

0.7 to 3.5

 

0.15

 

 

 

 

 

 

 

 

5 to 7

 

 

2

 

 

Table 12.7 Leakage circuit breaker selection example

 

 

 

 

Rated sensitivity

Servo amplifier

 

current of leakage

 

 

 

 

circuit breaker [mA]

MR-J2S-10B to MR-J2S-350B

15

MR-J2S-10B1 to MR-J2S-40B1

 

 

MR-J2S-500B

 

30

 

 

 

MR-J2S-700B

 

50

 

 

 

 

 

 

12 - 33

Page 164
Image 164
Bose MR-J2S- B instruction manual Leakage current breaker Selection method