Chapter 6 - Parameter description [FU1]

Motor Current].

Output Current

FU1-54 [OL Level]

Time

FU1-54 [OL Level]

AXA-AXC

 

 

 

 

 

ON

 

Time

 

t1

t1

 

 

 

 

t1: FU1-55 [Overload Warning Time]

[Overload Warning]

Related Functions: FU2-33 [Rated Motor Current]

I/O-44 [Multi-function Auxiliary Contact

Output]

FU1-56: Overload Trip Selection

FU1-57: Overload Trip Level

FU1-58: Overload Trip Delay Time

FU1► OLT select

 

 

56

 

1

 

56

--- Yes ---

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Factory Default:

Yes

 

 

1

 

 

 

 

 

 

 

 

 

 

 

FU1► OLT level

 

 

57

 

180

 

57

 

180 %

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Factory Default:

180 %

 

 

 

180

 

 

 

 

 

 

 

 

 

 

 

FU1► OLT time

 

 

58

 

60.0

 

58

60.0 sec

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Factory Default:

60.0 sec

 

 

60.0

 

 

 

 

 

 

 

 

 

 

Inverter cuts off its output and displays fault message when the output current persists over the FU1-57 [Overload Trip Level] for the time of FU1-58 [Overload Trip Time]. This function protects the inverter and motor from abnormal load conditions.

Note: The set value is the percentage of FU2-33 [Rated Motor Current].

Output Current

FU1-57 [OLT Level]

Time

FU1-57

[OLT Level]

FU1- 58 [OLT Time]

Output Frequency

Overload Trip

Time

[Overload Trip Operation]

Related Functions: FU2-33 [Rated Motor Current]

FU1-59: Stall Prevention Mode Selection (Bit set)

FU1-60: Stall Prevention Level

FU1► Stall prev.

 

59

 

000

 

59

000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Factory Default:

000

 

 

 

000

 

 

 

 

 

 

 

 

This bit set parameter follows the conventions used in I/O- 15 and I/O-16 to show the ON (bit set) status.

FU1► Stall level

 

60

 

180

 

60

180 %

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Factory Default:

180 %

 

 

180

 

 

 

 

 

 

 

 

This function is used to prevent the motor from stalling by reducing the inverter output frequency until the motor current decreases below the stall prevention level. This function can be selected for each mode of acceleration, steady speed, and deceleration via bit combination.