Use the inverter under the following environmental conditions:

 

Ambient

- 10 ~ 40 (non-freezing)

 

temperature

 

 

Relative

90% RH or less (non-condensing)

Environment

humidity

 

Storage

- 20 ~ 65

temperature

 

Location

Protected from corrosive gas, combustible gas, oil mist or dust

Altitude,

Max. 1,000m above sea level, Max. 5.9m/sec2 (0.6G)

 

 

Vibration

or less

 

Atmospheric

70 ~ 106 kPa

 

pressure

 

 

(2)Wiring

Do not connect a power factor correction capacitor, surge suppressor, or RFI filter to the output of the inverter. The connection orientation of the output cables U, V, W to the motor will affect the direction of rotation of the motor.

Incorrect terminal wiring could result in the equipment damage. Reversing the polarity (+/-) of the terminals could damage the inverter.

Only authorized personnel familiar with CMC inverter should perform wiring and inspections.

Always install the inverter before wiring. Otherwise, you may get an electric shock or have bodily injury.

(3)Trial run

Check all parameters during operation. Changing parameter values might be required depending on the load. Always apply permissible range of voltage to the each terminal as indicated in this manual. Otherwise, it could lead to inverter damage.

(4)Operation precautions

When the Auto restart function is selected, stay away from the equipment as a motor will restart suddenly after an alarm stop.

The Stop key on the keypad is valid only when the appropriate function setting has been made. Prepare an emergency stop switch separately.

If an alarm reset is made with the reference signal present, a sudden start will occur. Check that the reference signal is turned off in advance. Otherwise an accident could occur.

Do not modify or alter anything inside the inverter.

Motor might not be protected by electronic thermal function of inverter.

Do not use a magnetic contactor on the inverter input for frequent starting/stopping of the inverter.

Use a noise filter to reduce the effect of electromagnetic interference. Otherwise nearby electronic equipment may be affected.

In case of input voltage unbalance, install AC reactor. Power Factor capacitors and generators may become overheated and damaged due to potential high frequency noise transmitted from inverter.