HP 30 30 manual Freq mode, Setting Range Description, Keypad-1

Models: 30 30

1 218
Download 218 pages 18.86 Kb
Page 88
Image 88

Chapter 6 - Parameter Description [DRV]

Setting Range

Description

LCD

7-Seg

 

Keypad

0

Run/Stop is controlled by Keypad.

Fx/Rx-1

1

Control Terminals FX, RX and 5G

control Run/Stop. (Method 1)

 

 

Fx/Rx-2

2

Control Terminals FX, RX and 5G

control Run/Stop. (Method 2)

 

 

Output Frequency

Forward

Time

Reverse

 

 

 

Forward Run

FX-CM

ON

 

 

 

 

 

 

 

Reverse Run

 

 

 

RX-CM

 

ON

 

[Drive Mode: ‘Fx/Rx-1’]

 

 

Output Frequency

Forward

Time

Reverse

 

 

 

Run/Stop

FX-CM

 

ON

 

 

 

 

 

 

 

 

Direction

 

 

 

RX-CM

 

ON

 

[Drive Mode: ‘Fx/Rx-2’]

 

 

DRV-04: Frequency or Torque Mode (Frequency / Torque Setting Method)

DRV►

Freq mode*

 

04

 

0

 

04

Keypad-1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Factory Default:

Keypad-1

0

 

 

 

 

 

 

 

 

 

*In Torque mode : LCD display: “Trque mode” 7 Segment: “04”

If the DRV-04 [Frequency or Torque Mode] is set to 2 (V1), 3 (I), 4 (V1+I), see the description of I/O-01~10 [Analog Voltage/Current input signal adjustment].

If FU2-39 is set to 4 (Sensorless_T) or 6

(Vector_TRQ), speed is displayed as the percent[%] to the rated torque. Torque command is settable in DRV-04 [Frequency or Torque Mode].

DRV-04 setting value is separately saved according to which control mode (Speed or Torque) is selected in FU2-39 [Control mode selection].

Setting Range

 

 

 

Description

LCD

7-Seg

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Frequency is set at DRV-00. The

 

 

frequency is changed by pressing

PROG

 

Keypad-1

0

key and entered by pressing

ENT

 

key.

 

 

 

The inverter does not output

the

changed

 

 

frequency until the

ENT

key is pressed.

 

 

Frequency is set at

DRV

-00. Press

Keypad-2

1

PROG

key and then by pressing the

,

key,

the inverter immediately outputs

 

 

the

changed frequency. Pressing the

 

 

ENT

key saves the changed frequency.

V1

2

Input

the frequency reference (0-10V) to

the “V1” control terminal. Refer to the I/O-

 

 

01 to I/O-05 for scaling the signal.

I

3

Input the frequency reference (4~20mA)

to the “I” control terminal. Refer to the

 

 

I/O-06 to I/O-10 for scaling the signal.

V1+I

4

Input the frequency reference (0~10V,

4~20mA) to the “V1”,“I” control terminals.

 

 

The ‘V1’ signal overrides the ‘I’ signal.

6-4