Chapter 5 - Parameter List

Code

Description

Keypad Display

Setting Range

 

Units

Factory

Adj.

Page

LCD

 

7-Segment

LCD

 

7-Segment

Default

During

 

 

 

 

 

Run

 

FU2-27

Delay Time

Retry Delay

27

0 to 60 [sec]

 

0.1

1.0 [sec]

Yes

6-2

Before Auto Restart

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FU2-28

Speed Search Hold Time

SS blk time

28

0 to 60 [sec]

 

0.1

1.0 [sec]

No

6-2

 

 

 

 

 

0.75kW

 

0

 

 

 

 

 

 

 

 

 

1.5kW

 

1

 

 

 

 

 

 

 

 

 

2.2kW

 

2

 

 

 

 

 

 

 

 

 

3.7kW

 

3

 

 

 

 

FU2-30

Rated Motor Selection

Motor select

30

5.5kW

 

4

-

18

No

 

7.5kW

 

5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

11.0kW

 

6

 

 

 

 

 

 

 

 

 

15.0kW

 

7

 

 

 

 

 

 

 

 

 

18.5kW

 

8

 

 

 

6-2

 

 

 

 

 

22.0kW

 

9

 

 

 

 

 

 

 

 

 

 

 

 

 

FU2-31

Number of Motor Poles

Pole number

31

2 to 12

 

 

1

4

No

 

FU2-32

Rated Motor Slip

Rated-Slip

32

0 t o10 [Hz]

 

0.01

 

No

 

FU2-33

Rated Motor Current

Rated-Curr

33

1 to 200 [A]

 

1

 

No

 

(RMS)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

19

 

 

FU2-34

No Load Motor Current

Noload-Curr

34

0.5 to 200 [A]

 

1

No

 

 

 

 

(RMS)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FU2-36

Motor Efficiency

Efficiency

36

70 to 100 [%]

 

1

 

No

 

FU2-37

Load Inertia

Inertia rate

37

0 to 1

 

 

1

0

No

 

FU2-38

Carrier Frequency

Carrier freq

38

1 to 15 [kHz]

 

1

5 [kHz]

Yes

6-2

 

 

 

 

 

V/F

 

0

 

 

 

 

 

 

 

 

 

Slip comp

 

1

 

 

 

 

FU2-39

Control Mode Selection

Control mode

40

Sensorless_S

 

2

-

V/F

No

6-2

Sensorless_T

 

3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Vector_SPD

 

4

 

 

 

 

 

 

 

 

 

Vector_TRQ

 

5

 

 

 

 

 

 

 

 

 

No

 

0

 

 

 

 

 

 

 

 

 

All

 

1

 

 

 

 

FU2-40

Auto Tuning

Auto tuning

41

Rs + Lsigma

 

 

-

No

No

 

 

 

 

 

 

Enc Test

 

 

 

 

 

 

 

 

 

 

 

Tr

 

 

 

 

 

6-2

FU2-4120

Stator Resistance of

Rs

42

0 to (depending on FU2-30) [ohm]

0.001

21

No

 

 

Motor

 

 

 

 

 

 

 

 

 

 

 

FU2-42

Leakage Inductance of

Lsigma

44

0 to (depending on FU2-30) [mH]

0.001

 

No

 

Motor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

18The rated motor is automatically set according to the inverter model name. If different, set the motor capacity connected.

19This value is automatically entered according to the rated motor set in FU2-30. If different, set the correct value of the motor.

20Code FU2-41 through FU2-46 appears only when FU2-39 is set to ‘Sensorless_X’ or ‘Vector_XXX’.

21This value is automatically entered according to the rated motor set in FU2-30. If different, set the correct value of the motor.

5-7

Page 67