Chapter 6 - Parameter Description [I/O]

Output Frequency

I/O-42

 

I/O-43 / 2

 

 

 

 

Time

AXA-AXC

CLOSED

Time

 

 

 

[AXA-AXC configured as ‘FDT-4’]

 

[FDT-5]

This is the inverted output of [FDT-4].

Output Frequency

I/O-42

 

 

I/O-43 / 2

 

 

 

 

 

 

Time

AXA-AXC

ON

ON

Time

 

 

 

 

[AXA-AXC configured as ‘FDT-5’]

 

[OL]

AXA-AXC is CLOSED when the output current has reached the FU1-54 [Overload Warning Level] for the FU1- 55 [Overload Warning Time].

Output Current

FU1-54 [OL level]

Time

FU1-54 [OL level]

AXA-AXC

 

 

 

 

 

 

 

 

 

 

 

 

ON

 

Time

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

t1

 

t1

 

 

t1: FU1-55 [Overload Warning Time]

[[AXA-AXC configured as ‘OL’]

Related Functions: FU1-54 [Overload Warning Level] FU1-55 [Overload Warning Time]

[IOL]

AXA-AXC is CLOSED when the output current is above the 150% of rated inverter current for 36 seconds. If this situation is continued for one minute, the inverter will cut off its output and displays ‘IOL’ (Inverter overload) Trip. See the nameplate for the rated inverter current.

Output Current

150% of Rated

Inverter Current

Time

150% of Rated

Inverter Current

AXA-AXC

 

 

 

 

 

 

 

ON

 

Time

 

36sec

 

 

 

 

 

 

 

 

 

 

 

 

24sec

 

[AXA-AXC configured as ‘IOL’]

[Stall]

AXA-AXC is CLOSED when the inverter is on the stall prevention mode.

Output Current

FU1-60 [Stall Level]

Time

FU1-60 [Stall Level]

Output Frequency

Time

AXA-AXC

 

 

 

 

 

CLOSED

 

Time

 

 

 

 

[AXA-AXC configured as ‘Stall’]

6-46

Page 138
Image 138
HP 30 30 manual FDT-5, Iol, Stall