Chapter 6 - Parameter Description [FU2]

4

DRV-04 [Frequency Mode]

5

DRV-05 [Step Frequency 1]

6

DRV-06 [Step Frequency 2]

7

DRV-07 [Step Frequency 3]

8

DRV-08 [Output Current]

9

DRV-09

[Motor Speed]

10

DRV-10

[DC link Voltage

11

DRV-11

[User Display selected in FU2-73]

12

DRV-12

[Fault Display]

FU2-73: User display selection

Related parameter : DRV-11 [User display selection]

Select the display as shown below in FU2-73 [User display selection].

 

Setting

 

 

FU2-73

 

 

Name

 

 

Description

 

 

0

 

 

Voltag

 

 

Output

 

 

Display output voltage of the

 

 

 

 

e

 

 

voltage

 

 

inverter (Factory setting)

 

 

 

 

 

 

 

 

 

 

 

1

 

 

Watt

 

 

Output

 

 

Display output power of the

 

 

 

 

 

 

power

 

 

inverter

 

 

 

 

 

 

 

 

 

 

 

Note) The display of “Watt” is approximate value.

FU2-74: Gain for Motor Speed Display

FU2► RPM factor

 

74

 

100

 

74

100 %

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Factory Default:

100 %

 

 

100

 

This code is used to change the motor speed display to rotating speed (r/min) or mechanical speed (m/min). The display is calculated by following equation.

Rotating speed = 120 x F / P, where F=Output frequency, P= motor pole number

Mechanical speed = Rotating speed x Motor RPM Display Gain

Related Functions: DRV-00 [Output Frequency]

DRV-09 [Motor Speed]

FU2-31 [Number of Motor Pole]

FU2-75: DB (Dynamic Braking) Resistor Mode Selection

FU2►

DB mode

 

 

75

 

 

1

 

 

75

Int. DB-R

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Factory Default:

 

Int. DB-R

1

 

 

 

This code is used to protect the DB resistor from over

 

heating.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Setting Range

 

 

 

Description

 

 

 

 

LCD

7-Seg

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

None

 

 

This is selected when there is no resistor

 

 

0

connected. At this time, inverter does not

 

 

 

 

 

generate DB turn on signal.

 

 

 

 

 

 

 

 

This is selected when using the internal

 

 

 

 

 

DB resistor. This must be selected for

 

Int. DB-R

 

1

1~5 HP inverters because they have

 

 

internal DB resistor as a default.

 

 

 

 

 

 

 

 

 

 

Enable Duty (%): 2 ~ 3 %

 

 

 

 

 

 

 

 

Continuous Turn On Time: 5 seconds

 

 

 

 

 

This is selected when using an external

 

 

 

 

 

DB resistor. This must be selected for

 

Ext. DB-R

 

 

7.5~10 HP inverters. This must be

 

 

2

selected for 1~5 HP inverters in case of

 

 

 

 

 

using an external DB resistor.

 

 

 

 

 

Enable Duty (%): 0 ~ 30 %

 

 

 

 

 

 

 

 

Continuous Turn On Time: 15 seconds

The inverter turns the DB turn on signal OFF when the Continuous Turn On Time expires during dynamic braking, and an over voltage fault can occur. When this happens, increase the deceleration time or install an external high- duty DB resistor.

Install an exterior high-duty DB resistor when the load accelerates and decelerates frequently. Set the FU2-75 [DB Resistor Mode selection] to ‘Ext. DB-R’, and set the FU2-76 [Duty of DB Resistor].

This does not apply to 15~30 HP inverters. They need the Optional DB unit to use DB resistor.

FU2-76: Duty of DB (Dynamic Braking) Resistor

FU2►

DB %ED

 

 

76

 

10

 

76

10 %

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Factory Default:

10 %

 

 

 

10

 

This must be set when using an external DB resistor. The

6-31

Page 123
Image 123
HP 30 30 FU2-73 User display selection, FU2-74 Gain for Motor Speed Display, FU2-76 Duty of DB Dynamic Braking Resistor