Chapter 7 - Options

7.1.2Terminal Configuration

+24V DC

24V

Ground

VR V2 5G NC Q1 Q2 Q3 EXTG NC P4 P5 P6 LM CM

7.1.3Terminal Description

 

Section

Terminal

Name

Description

 

 

P4, P5, P6

Multi-Function Input

Used as the extended function of P1, P2, P3

 

Contact Input

(I/O-12 ~ I/O-14)

 

 

 

Input

 

CM

Common Terminal

Common terminal for P4, P5, P6

Analog

VR

Power Supply for V2

DC voltage output terminal for V2 (+12V, 10mA)

 

 

Frequency

V2

Analog Voltage Input

Analog voltage input terminal for frequency reference or override.

 

Reference

5G

Common Terminal

Common terminal for VR and V2

 

 

 

 

Used to monitor one of Output Frequency, Output Current, Output

 

+15V Pulse

LM

Load Meter

Voltage, DC link Voltage.

Output

Output

 

 

(+15V Pulse output, Average voltage: 0 ~ 10V DC)

 

CM

Common Terminal

Common terminal for LM

Open Collector

Q1, Q2, Q3

Multi-Function Output

Used as the extended function of AXA, AXC (I/O-44)

 

 

(Open-Collector Output)

 

Output

 

 

 

EXTG

External Common Terminal

Common terminal for Q1, Q2, Q3

 

 

 

 

NC

Not Used

 

7.1.4Parameters of Sub-A Board

Code

Parameter Description

Code

Parameter Description

EXT-01

Sub Board Type Display

EXT-09

Analog Voltage Input Signal (V2) Adjustment

EXT-02

 

EXT-10

 

 

EXT-03

Multi-Function Input Terminal (P4, P4, P6) Define

EXT-30

 

EXT-04

 

EXT-31

Multi-Function Output Terminal (Q1, Q2, Q3) Define

EXT-05

V2 Mode Selection

EXT-32

 

EXT-06

Filtering Time Constant for V2 Input Signal

EXT-34

LM Output Adjustment

EXT-07

Analog Voltage Input Signal (V2) Adjustment

EXT-35

 

EXT-08

 

 

 

 

 

7-5

Page 167
Image 167
HP 30 30 manual Options Terminal Configuration, VR V2 5G NC Q1 Q2 Q3 Extg NC P4 P5 P6 LM CM, Terminal Description